TitlePVDescription
Sweep start:SEQ:n:START_FREQ_SThis sets the initial frequency for the swept NCO.  All frequencies are in multiples of the machine revolution frequency.  The super sequencer offset is added to the sweep frequency.
Sweep step:SEQ:n:STEP_FREQ_SThis sets the frequency advance when the sequencer steps from one dwell period to the next.
Sweep end:SEQ:n:END_FREQ_SThis is automatically set to start+step*capture, and is automatically updated any time any of those values changes.  If this PV is written to then step will be computed (as (end-start)/capture) and this PV will update.
Capture:SEQ:n:COUNT_SThis configures the number of dwells in this sequencer state.
Holdoff (state):SEQ:n:STATE_HOLDOFF_SThis number of turns is added to the start of this sequencer state after the initial sweep frequency has been configured.  The detector is disabled for the duration of this holdoff period.
Holdoff (dwell):SEQ:n:HOLDOFF_SThis number of turns is added to the start of the dwell time after the swept frequency has been stepped.  The detector is disabled for the duration of the holdoff period, which can be used to give time for the swept system to settle to the new frequency.
Dwell time:SEQ:n:DWELL_SThis configures the number of turns for which the sweep frequency is driven and the detector is operated for a single sample.
NCO Magnitude:SEQ:n:GAIN_S, :SEQ:n:ENABLE_SThis determines the gain of the swept NCO excitation in 6dB steps, with 0dB corresponding to full scale DAC excitation.  :ENABLE_S must be set to "On" for a signal to be generated.
Bunch Bank:SEQ:n:BANK_SThis determines which of the four available bunch configuration banks is selected during the operation of this state.
Blanking:SEQ:n:BLANK_SIf this is set to "Blanking" then the detector will be temporarily disabled during the blanking window and the dwell time will be extended.
Data window:SEQ:n:ENWIN_SIf this is set to "Windowed" then the detector data will be multiplied by the data window configured in Detector Window Setup.
Tune PLL:SEQ:n:TUNE_PLL_SIf this is set to "Follow" then the Tune PLL offset will be continuously added to the sweep NCO frequency.  This is designed to allow a swept tune to track dynamic changes in the tune.
Data capture:SEQ:n:CAPTURE_SThis determines whether the detector is active during this sequencer state.

...