This page shows a top level overview of the status of the selected axis.  On this screen we see the following information and controls (all PVs are prefixed with $(device):$(axis) unless indicated otherwise).

TitlePVDescription
System Status:STATUSThis indicates the aggregate health of the digital processing chain for this axis.  Clicking on this will bring up the System Status page where the source of any alarm indication here can be located.

:SEQ:MODEThis field shows a brief summary of the sequencer setup, in the example above it says "Sweep: all bunches (-42dB)", which means a multi-bunch sweep over all bunches with an excitation strength of -42dB over all bunches.
Feedback Settings:FIR:GAIN_SThis controls the overall level of FIR gain.

:FIR:0:PHASE_SThis controls the phase of the FIR filter for FIR #0

:BUN:MODEThis shows a brief summary of the feedback status when the sequencer is not running, in the illustrated example feedback is not active.
Bunch motion standard deviation:ADC:MMS:STDThis shows the standard deviation of bunch motion for this axis, see Min/Max/Sum for more detail.
System
This button brings up the MBF System View providing links to all other control pages.
Tune, Phase$(prefix):TUNE, $(prefix):PHASEThese two PVs are provided by the tune fitter from the data captured by detector #0.  Clicking on this will bring up the Tune Fitting Overview page.
Tune Only, Tune Special, Feedback On & Tune
These three buttons will automatically configure the selected axis for feedback and tune sweep as appropriate and as configured.

...